VRF HP to TR Converter

Convert VRF and VRV outdoor unit horsepower into tons of refrigeration, kilowatts and BTU/h — using the commercial 2.8 kW per HP convention, not the residential one.

VRF Outdoor Unit Capacity
Cooling capacity
tons of refrigeration

A consultant's schedule says "16 HP outdoor unit". The client's brief is written in tons. The electrical drawing wants kilowatts. Three units, one machine, and a conversion factor that's not the same one used for residential split systems — which is exactly where the errors creep in.

Quick answer: 1 VRF HP ≈ 2.8 kW cooling ≈ 0.8 TR ≈ 9,550 BTU/h. So a 10 HP outdoor unit is about 28 kW, 8 tons, or 95,500 BTU/h.

Where the 2.8 kW per HP Convention Comes From

VRF sizing in horsepower is a Japanese inheritance. Daikin's VRV line — the system that created the category in 1982 — designated outdoor units by HP, and the rest of the industry followed so that specifications stayed comparable across brands.

The number isn't derived from anything mechanical. It is a product-line convention, and it holds up well against published data:

Nominal sizePublished rated coolingImplied kW per HP
8 HP22.4 kW2.80
10 HP28.0 kW2.80
12 HP33.5 kW2.79

Consistent to within a fraction of a percent. That's why 2.8 kW/HP works as a planning figure — but for a tender or a load check, always read the rated capacity from the manufacturer's engineering data for the specific model and series, because ratings shift slightly between generations and between 50 Hz and 60 Hz markets.

Formulas
TR = VRF HP × 0.796
kW = HP × 2.8 · BTU/h = HP × 9,554 · HP = TR × 1.256
Based on 1 TR = 12,000 BTU/h = 3.51685 kW and the 2.8 kW per HP VRF convention

VRF HP to TR, kW and BTU Table

Planning values across the standard outdoor unit range, including the modular combinations used for larger systems.

HPkW (cooling)Tons (TR)BTU/hTypical application
411.23.238,200Small office floor
514.04.047,800Apartment / clinic
616.84.857,300Retail unit
822.46.476,400Small commercial floor
1028.08.095,500Office floor plate
1233.69.6114,700Restaurant
1439.211.1133,800Mid-rise floor
1644.812.7152,900Hotel wing
1850.414.3172,000Large floor plate
2056.015.9191,100Single-module maximum
2467.219.1229,300Two modules combined
3084.023.9286,600Multi-module system
36100.828.7343,900Large multi-module
42117.633.4401,300Three modules combined

VRF HP Is Not the Same as Residential Split HP

This is the single most common source of confusion, and it produces a consistent 6% error if you get it backwards.

LabelCooling per HPIn tonsWhere you see it
VRF / VRV HP≈ 2.8 kW0.80 TRCommercial outdoor units, consultant schedules
Residential split HP≈ 2.64 kW (9,000 BTU/h)0.75 TRRetail showrooms in PH, MY, ID, HK
Mechanical horsepower0.746 kW of shaft powerMotors and engines — not a cooling unit at all

Three different quantities wearing the same two letters. A 10 HP VRF unit is about 28 kW; ten residential "1 HP" splits would total about 26.4 kW; and ten mechanical horsepower is 7.46 kW of shaft work, which has nothing to do with cooling at all. For the residential convention see ton to HP and the aircon conversion chart.

Why Indoor HP Does Not Add Up to Outdoor HP

Add up the indoor units on a VRF schedule and the total will usually exceed the outdoor unit rating — often by 10–30%. That's deliberate, not a mistake on the drawing.

The design parameter is connection ratio (also called diversity): total connected indoor capacity ÷ outdoor capacity. Manufacturers typically permit somewhere between about 50% and 130%, and the logic is that rooms don't peak simultaneously. A west-facing office peaks late afternoon; the east side peaked at 10 a.m.; the meeting room only loads when occupied.

  • Under 100% — outdoor unit has headroom; every zone can run flat out at once. Used where simultaneous peak is real, such as data or process rooms.
  • 100–130% — the normal commercial case. Cheaper plant, relies on genuine diversity in the occupancy pattern.
  • Over the manufacturer's limit — not permitted, and in practice means every zone underperforms on the hottest afternoon of the year.

So when you convert HP to tons for a capacity check, be clear which number you're converting: outdoor unit capacity is what the plant can deliver; connected indoor capacity is what the terminals could theoretically demand.

A Note on Heating Capacity

Heat-pump VRF outdoor units are usually rated slightly higher in heating than in cooling at nominal conditions — but that heating figure falls as outdoor temperature drops, and defrost cycles reduce delivered output further. Never size a heating application from the cooling HP figure alone; use the manufacturer's capacity tables at your design outdoor temperature.

For general refrigeration conversions use ton to HP, BTU to HP and HP to ton. Cooling capacity in metric is handled by cooling kW to HP, and for electrical consumption rather than capacity see aircon HP to watts.

For residential split systems rather than commercial VRF plant, AC horsepower uses the 9,000 BTU per HP convention instead.

How this converter works and its limits

We convert using 1 ton of refrigeration = 12,000 BTU/h = 3.516853 kW, and the VRF industry convention of about 2.8 kW of rated cooling per nominal horsepower. That convention is validated against published outdoor-unit ratings — 8 HP at 22.4 kW, 10 HP at 28.0 kW and 12 HP at 33.5 kW all imply 2.79–2.80 kW per HP. It is a planning figure only: actual rated capacity varies by manufacturer, product series, refrigerant, supply frequency and rating condition, and heating capacity follows a different curve entirely. For tender documents, load calculations or commissioning, use the rated capacity published in the manufacturer's engineering data for the specific model at your design conditions. Connection ratio limits are set by each manufacturer and must be taken from their design manual.

Frequently Asked Questions

About 0.8 TR — roughly 2.8 kW of cooling, or 9,550 BTU/h.

Multiply by 0.8. A 10 HP unit ≈ 8 tons; a 20 HP unit ≈ 16 tons. For a specific model, divide its rated kW by 3.51685.

Different markets. Residential 1 HP ≈ 9,000 BTU/h (2.64 kW); VRF 1 HP ≈ 2.8 kW. A 10 HP VRF unit is roughly 6% bigger than ten residential horsepower.

28 kW rated cooling — 8 tons, 95,500 BTU/h. Published 8/10/12 HP ratings are commonly 22.4, 28.0 and 33.5 kW.

No — it is a nominal capacity class. A 10 HP outdoor unit typically draws around 6–8 kW at rated conditions, nowhere near ten mechanical horsepower.

Connected indoor capacity ÷ outdoor capacity, commonly allowed from ~50% to ~130%. Rooms rarely peak together, so indoor HP totals deliberately exceed outdoor HP.

Multiply tons by 1.256. A 20 ton load ≈ 25 HP, which in practice is met by combining standard modules.

No. It is the cooling rate needed to freeze one short ton of water in 24 hours — 12,000 BTU/h or 3.51685 kW. A rate, not a mass.